Thesis
Analysis and detection of tap changes on power systems
- Abstract:
-
Demand side management (DSM) is a key concept for the successful implementation of smart grids. In order to achieve DSM, the users need information about local network stress and one approach to detecting network stress is to monitor the on- load tap changers (OLTC) within the network, since tap changes play an important role in voltage regulation in power system and can reflect the variation of load. This thesis focuses on the analysis, modelling and detection of tap changes.
After an introduction on power systems and the OLTC transformer, an algorithm is proposed that can be used for measuring the frequency of the three phase sinusoidal voltage signal in power system. The frequency estimation algorithm contains two parts. The first part is a HTPLL or filtering algorithm that uses the Prism methodology, which provides an initial frequency estimate. The second part is a complex least mean square (CLMS) algorithm that can refine the initial frequency estimate. The proposed frequency estimation algorithm is tested with both simulated and real data and compared with other algorithms, showing that the proposed algorithm can give improved performance.
In the third chapter, an algorithm for tap change detection is introduced. The algorithm is divided into three parts. The first part is a Hilbert-transform phase- locked loop (HTPLL), which is used to estimate the frequency of the voltage signal. The second part is a QR-decomposition windowed recursive least squares algorithm, which is used to estimate the amplitude of the voltage signal. The last part is a hypothesis test that can distinguish tap changes from the variation in the voltage magnitude from the voltage fluctuation caused by changes in the load. The algorithm is tested with both simulated and real data, showing that the algorithm is capable of detecting tap changes from the voltage signal.
In the fourth chapter, models of tap changer, generator and load buses are introduced which can be used for studying the interaction between tap changes and variations in the load. We investigate di erent tap changer modelling methods and propose a quantised tap changer model, which combines a linear dynamic function with a quantiser. This model evolves in continuous time but has a quantised number of tap positions. The response of di erent tap changer models are simulated, demonstrating that the quantised tap changer is suitable for power system analysis.
Actions
Access Document
- Files:
-
-
(Preview, Archive version, pdf, 11.8MB, Terms of use)
-
Authors
Contributors
+ Duncan, S
- Institution:
- University of Oxford
- Division:
- MPLS
- Department:
- Engineering Science
- Role:
- Supervisor
- ORCID:
- 0000-0002-9525-7305
- DOI:
- Type of award:
- DPhil
- Level of award:
- Doctoral
- Awarding institution:
- University of Oxford
- Language:
-
English
- Keywords:
- Subjects:
- Deposit date:
-
2025-09-14
- ARK identifier:
Terms of use
- Copyright holder:
- Xiaoqing Chen
- Copyright date:
- 2018